Page 27
4-11
Installation & Operation Manual
Quick Setup
Full Scale Flow This parameter sets the maximum flow the system is expected to measure. This parameter has
influence on other system parameters. These parameters include:
• Frequency Output – Full scale frequency is observed at full scale flow
• Low Flow Cutoff – Changes to full scale flow affect the measuring cut-off threshold of the meter
• Alarm Outputs – Changes to full scale flow adjusts the thresholds for generating set point alarms
• Pulse Outputs – Changes to full scale flow adjusts the pulse frequency and duty cycle
• Analog Outputs – Changes to full scale flow adjusts the interpretation of the analog output signal
Change the full scale flow based on the meter size and the applications requirements. Verify that the
full scale flow falls within the meter’s suggested flow range limits. In terms of flow velocity, the meter's
limits are from 0.1 to 39.4 feet/second.
The full scale flow is valid for both flow directions.
Note: If the flow rate exceeds the full scale setting, an error message indicates that the
configured full scale range has been exceeded. However, the meter will continue to measure.
This will affect the latency of the pulse outputs and possibly cause overflow. Furthermore,
the analog output may also be placed in alarm mode.
To set or change the Full Scale Flow, follow these steps from the Quick Setup menu:
1. Select Full Scale Flow to view the Full Scale Flow display.
2. Set the full scale flow value to the desired setting.
3. Press [E] to save the full scale flow value and return to the Measurements menu.
Low Flow Cutoff Low flow cutoff defines the threshold at which flow measurement will be forced to zero. The cutoff
value can be set from 0% to 10% of the full scale flow. Increasing this threshold will help prevent false
readings during “no flow conditions possibly caused by pipe vibration or inherent system noise.
To change Low Flow Cutoff, follow these steps from the Low Flow Cutoff display.
1. Set the Low Flow Cutoff value to the desired setting, between 0% and 10%.
2. Press [E] to save the value.

Table of Contents

Other manuals for Badger Meter M Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Badger Meter M Series and is the answer not in the manual?

Badger Meter M Series Specifications

General IconGeneral
BrandBadger Meter
ModelM Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals