Page 52
4-11
Model M-2000 Mag Meter
Menu Manager Conguration Errors
Error Description Recommended Action
110 Output 1/2: Pulse Output
Conguration Error
This error is observed when improperly conguring the full scale ow, pulse per unit, or pulse width.
This error can indicate the following conguration violations:
1. Pulse frequency exceeds limits at full scale ow
2. Pulse duty cycle is less than 50% at full scale ow (pulse on time > pulse o time)
Pulse frequency limit is 10 kHz. However, with a non-zero pulse width conguration, the limit is 500
Hz to achieve a 50% pulse duty cycle.
If not using the pulse outputs, set the pulses per unit to zero to allow for reconguration of the full
scale ow. If it is required to use the pulse outputs, reevaluate the pulse output conguration.
Consider recording and clearing totalizers prior to changing totalizer units.
120 Display: Totalizer Conversion
Error – Totalizer cannot be properly
converted for display
This error is observed while trying to change the totalizer units. Limits of display will prevent
improper conguration of the volume unit dependent on current totalizer values. Consider
recording and cleaning totalizers prior to changing totalizer.
121 Output 1/2: Pulse Output
Conguration Error
This error is observed when changing the totalizer units of measure. This error implies the pulse
conguration exceeds limits (see error 110). Please note the pulses per unit is not automatically
updated on volume unit reconguration. The pulses per unit should be manually changed to
accommodate the desired units of measure. It may be necessary to set the pulses per unit to zero
then change to the desired totalizer units.
140 Output 3: Conguration Error – Full
scale frequency exceeds limits of
relay (1000 Hz)
Reduce full scale frequency setting of output when hardware is congured for relay operation.
150 Output 3: Conguration Error – Full
scale frequency exceeds limits (10
kHz)
Reduce full scale frequency setting of output when hardware is congured for open collector
operation.
Display Error / Status Messages
Error Message Possible Cause Recommended Action
Err: Detector No detector connection with amplier. Check detector and cable connections in accordance with this manual.
Connection between amplier and detector Contact Technical Support.
Supply voltage too low. Contact Technical Support.
Grounded coils in meter. Contact Technical Support.
Water in detector. Contact Technical Support.
Err: Empty pipe Pipe may not be full. Make sure all trapped air is out of system.
If uid or uid conductivity recalibrate the parameter.
Err: Full scale Actual ow rate is exceeding programmed ow. Reduce ow rate or increase the programmed full scale value by more than 5%.
Err: AD-Range AD-Converter is exceeding signal limits. Check the grounding scheme of the meter installation. See grounding section in
this manual. Verify pipe is not empty.
Err: AD-INT Initialization of AD-Converter unsuccessful. Contact Technical Support.
Err: Rollover Rollover counters have exceeded limit. Clear all totalizers.
Err: Rollover Status Totalizer rollover has occurred. Reload totalizer then clear all totalizers.
Err: Simulation I/O simulator is enabled. Disable simulator in I/O menu.