2100-444-003A
Page 28
down respectively through the above screen showing four lines at a time.
5.3.1.1 ROOM TEMPERATURE
The room temperature item displays the current temperature inside the structure.
5.3.1.2 ROOM HUMIDITY
The room humidity item displays the current humidity inside the structure. This is an optional
sensor and may or may not be present in your system. The current value will read one percent, "1 %" if
no sensor is present.
5.3.1.3 OUTDOOR TEMPERATURE
The outdoor temperature item displays the current temperature outside the structure.
5.3.1.4 OUTDOOR HUMIDITY
The outdoor humidity item displays the current humidity outside the structure.
5.3.1.5 ACTIVE COOLING SETPOINT
The Active Cooling Setpoint displays the current cooling setpoint that the controller using to
determine whether cooling is required or not. If the Zone temperature is above the Active Cooling
Setpoint, Stage One Cooling will be on.
The Active Cooling Setpoint will be one of three values. If the controller is in occupied mode,
the Active Cooling Setpoint will be the same as the Occupied Cooling Setpoint. If the controller is in
unoccupied mode, the Active Cooling Setpoint will be the same as the Unoccupied Cooling Setpoint.
Occupancy is determined from the After-hours Occupancy Override Button located on the temperature
sensor on the front of the TCS22. If the controller is in Dehumidification mode, the Active Cooling
Setpoint will be 73
o
the same as the fixed Dehumidification Cooling Setpoint.
5.3.1.6 ACTIVE HEATING SETPOINT
The Active Heating Setpoint displays the current heating setpoint that the controller using to
determine whether heating is required or not. If the Zone Temperature is below the Active Heating
Setpoint, Stage One Heating will be on.
The Active Heating Setpoint will be one of three values. If the controller is in occupied mode, the
Active Heating setpoint will be the same as the Occupied Heating Setpoint. If the controller is in
unoccupied mode, the Active Heating Setpoint will be the same as the Unoccupied Heating Setpoint.
Occupancy is determined from the After-hours Occupancy Override Button located on the temperature
sensor on the front of the TCS22. If the controller is in Dehumidification mode, the Active Heating