5.3.3.7 FIRE TROUBLE
The Fire Trouble alarm item monitors the fire alarm system in the structure. A "None" alarm
message indicates that no alarm is present and that the fire alarm system is operating normally. A "Fault"
alarm message indicates that an alarm is present and the fire alarm system is malfunctioning.
This is a self-clearing alarm and will reset itself when the alarm condition no longer exists. This
is a medium priority alarm.
5.3.3.8 FIRE ALARM
The Fire Alarm item monitors the fire alarm system in the structure. A "None" alarm message
indicates that no alarm is present and that the fire alarm system has not detected a fire. A "Fault" alarm
message indicates that an alarm is present and that the fire alarm system has detected a fire in the
structure.
This is a self-clearing alarm and will reset itself when the alarm condition no longer exists. This
is a critical priority alarm.
5.3.3.9 OUTDOOR TEMP ALARM
The Outdoor temperature alarm item will show one of two different alarm messages. A No alarm
message indicates that the Outdoor Temperature Sensor is functioning normally. A Fault alarm message
indicates that the Outdoor Temperature Sensor is sensing a value above 120 F
o
or below -20 F
o
. This
probably indicates a faulty sensor.
These are all self-clearing alarms and will reset themselves when the alarm condition no longer
exists. This is a critical alarm.
5.3.3.10 OUTDOOR HUMIDITY ALARM
The Outdoor Humidity Alarm item will show one of two different alarm messages. A No alarm
message indicates that the Outdoor Humidity Sensor is functioning normally. A Fault alarm message
indicates that the Outdoor Humidity Sensor is sensing a value above 99 % RH or below 2 % RH. This
probably indicates a faulty sensor. When a Outdoor Humidity Fault alarm is detected, the Outdoor
Humidity value defaults to 50 % RH until the sensor is replaced.
These are all self-clearing alarms and will reset themselves when the alarm condition no longer
exists. This is a medium priority alarm.
5.3.3.11 DOOR ALARM
The Door Alarm item monitors the door switch in the structure. A "None" alarm message
indicates that no alarm is present and that the door is closed. A "Fault" alarm message indicates that an
alarm is present and that the door in the structure is open.
This is a self-clearing alarm and will reset itself when the alarm condition no longer exists. This
is a critical priority alarm.