Louis RamosAug 1, 2025
What to do if the red error LED is lighting up on Baumuller Control Unit?
- AandrewjacksonAug 1, 2025
If the red error LED is illuminated, it indicates an error. You can address this in several ways: * Using ProDrive (from FW 3.07), click the “Quit errors” button in the “Device manager” dialog box or on the “Device manager” page to acknowledge and address the error. * By writing access to control word (P0300), generate a rising edge in bit 7. * Configure a digital input of a DIO module via parameter P0575 for error reset. * Use the pulse enable input, assuming the drive is controlled solely via hardware inputs.