EasyManuals Logo

Baxi DUO-TEC COMPACT User Manual

Baxi DUO-TEC COMPACT
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
13
INSTALLER Section (en)
7710400 (01-06/18)
12.4 COMBUSTION TEST (CO
2
%)
For correct boiler operation, the content of (CO
2
- O
2
) in the combustion fumes must observe the tolerances indicated in the
following table. If the value of (CO
2
- O
2
) is different, check the electrodes and their relative distances. If necessary, replace the
electrodes and position them correctly. If the problem persists, use the following function.
G20 G31
CO
2
% O
2
% CO
2
% O
2
%
Maximum power
Nominal value 8.7 5.4 10.0 6.0
Permitted value 8.2 - 9.3 6.3 - 4.3 9.5 - 10.5 6.8 - 5.2
Ignition power
Nominal value 8.7 5.4 10.8 4.8
Permitted value 8.2 - 9.3 6.3 - 4.3 10.3 - 11.3 5.5 - 4.1
Minimum power
Nominal value 8.8 5.2 10.0 6.0
Permitted value 8.2 - 9.3 6.3 - 4.3 9.5 - 10.5 6.8 - 5.2
The
CO
2
/O
2
values are with the cover closed.
The combustions analisys shall be done using an analyzer regularly calibrated.
During normal operation the boiler performs combustion control cycles. In this phase, CO values higher than 1000 ppm can
occur for brief periods of time.
COMBUSTION ADJUSTMENT FUNCTION (CO
2
%)
This function sets out to partially adjust the value of CO
2
%. The following procedure is used.
Press buttons and together for at least 6 seconds. When the function is enabled, the displays shows Onfor a few
seconds followed by programme row “304” alternated with the % of boiler power.
After the burner is lit, the boiler reverts to maximum DHW power (100). When the display shows "100" it is possible to partially
adjust the value of CO
2
%;
press
. The display shows "00" alternating with the function number "304" ( ashes);
press
to raise or lower the amount of CO
2
(from -5 to +5).
press
to save the new value and view the power value "100" on the display again (the boiler continues operating at
maximum DHW power).
This procedure can also be used to adjust the quantity of CO
2
to the ignition power and to the minimum power by pressing
after point 5 of the procedure described above.
After saving the new value (point 5 of the procedure), press to take the boiler to its ignition power. Wait for the value of
CO
2
to stabilise and then adjust as described in point 4 of the procedure (the power value is a number <> 100 and <> 0) then
save (point 5).
press
again to take the boiler to minimum power. Wait for the value of CO
2
to stabilise and then adjust as described in
point 4 of the procedure (power value = 00);
to exit the function, press the buttons for at least 6 seconds as described in point 1.
13. GAS VALVE
This appliance does not require any mechanical adjustment on the valve. The system ensures electronic auto-adaptation.
Gas valve key
Pi
Gas supply inlet pressure tap
13.1 GAS CONVERSION METHODS
Only an Authorised Technical Assistance Service can convert boiler operation from NATURAL GAS to LPG or vice-versa. To
perform calibration, set parameter P02 as described in the PARAMETER SETTINGS section. Lastly, check the combustion
parameters as described in the SPECIAL FUNCTIONS - CHECKING COMBUSTION PARAMETERS section.
When the gas change is completed the boiler data plate must be amended to indicate the new gas data.
Pi

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Baxi DUO-TEC COMPACT and is the answer not in the manual?

Baxi DUO-TEC COMPACT Specifications

General IconGeneral
ModelDUO-TEC COMPACT
CategoryBoiler
TypeCombi
MountingWall-mounted
Gas TypeNatural Gas / LPG
NOx Class5
Output24 kW
Dimensions700 x 400 x 295 mm
Weight32 kg
Modulation1:7

Related product manuals