4233 5000 13
83
Data at 10 bar inlet pressure
Unit dMED
025
dMED
035
dMED
045
dMED
075
dMED
090
Volume flow at dryer inlet l/min 960 1360 1760 2920 3480
Volume flow at dryer inlet cfm 33.9 48.7 61.4 103.8 122.9
Pressure drop over dryer mbar
646
926
722
757
644
Pressure drop over dryer psi
9,37 13,4 10,47 10.98 9.34
Time of half a cycle s
154 154 154 154 154
Regeneration time s
120 120 120 120 120
Pressurization time s
34
34
34
34
34
Installed power W
340 340 340 340 340
Net mass kg
220
240 280 320 360
Net mass lb
485
529 617 703 794
Air quality (Pharmacopeia)
O
2
concentration
%
20<X<
22
CO
2
concentration
ppm
500
CO concentration
ppm
5
SO
2
concentration
ppm
1
NO
x
concentration
ppm
2
Pressure dew point
°C
-31
Pressure dew point
°F
-23.8
Oil vapour
mg/m³
0.1
Taste and odour
free
Unit
dMED
110
dMED
150
dMED
220
dMED
300
Volume flow at dryer inlet l/min 4280 5830 8520 11640
Volume flow at dryer inlet cfm 150.4 192.8 300.8 411
Pressure drop over dryer mbar 660 700 820 800
Pressure drop over dryer psi 9,57 10,15 11,89 11,60
Time of half a cycle s
154 154 154 154
Regeneration time s
120 120 120 120
Pressurization time s
34 34 34 34
Installed power W
340 340 340 340
Net mass kg
450 510 650 760
Net mass lb
992
1124
1433
1675
Air quality (Pharmacopeia)
O
2
concentration
%
20<X<
22
CO
2
concentration
ppm
500
CO concentration
ppm
5