Extended functions
BK3xx082 Version: 4.3.0
State transitions in the Bus Coupler
If the PROFIBUS DP configuration received does match the Bus Terminal configuration in multi-configuration
mode, the Bus Coupler sets the "static diagnostics" bit in the PROFIBUS DP diagnostic data and delays the
execution of a terminal bus cycle (I/O RUN LED remains off). As soon as the terminal assignment (activated/
not activated) has been written by the PROFIBUS DP master, the Bus Coupler again carries out an
examination of the PROFIBUS DP configuration, and automatically enters cyclic data exchange (the "static
diagnosis" bit in PROFIBUS DP diagnostic data is cleared, and the terminal bus cycle is executed cyclically
(the I/O-RUN LED goes on during the terminal cycle)). Furthermore, the terminal assignment is stored in the
non-volatile memory of the Bus Coupler, so that during a restart of the PROFIBUS DP, the PROFIBUS DP
master does not have to write the terminal configuration again.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Beckhoff BK3150 and is the answer not in the manual?

Beckhoff BK3150 Specifications

General IconGeneral
Product NameBK3150
CategoryAdapter
ManufacturerBeckhoff
FieldbusPROFIBUS
Bus SystemPROFIBUS DP
Number of Bus Terminals64
Operating Voltage24 V DC (-15%/+20%)
Current Supply24 V DC
Operating Temperature0°C to +55°C
Storage Temperature-25°C to +85°C
Relative Humidity95%, no condensation
Protection ClassIP20
Number of Terminals64
Weightapprox. 160 g
Current Consumption70 mA
Data Transfer Rates9.6 kbit/s to 12 Mbit/s