Installation
CP6700-0001-00x0/ CP6706-0001-00x0 17
3.3.4 Configuration for shutting down the PC
The connections for shutting down the Industrial PCs are established via the PC_ON input and the Power
Status output.
3.3.5 PC_ON and Power Status functions
If the PC_ON input is connected to 24 V via a switch, the PC shuts down according to the rules. The
PC_ON signal is inverted, i.e. the PC shuts down if the 24 V connection is live.
Once the PC has shut down, the Power Status output is switched from 24 V to 0 V. Via this output a
signal lamp can be connected or a contactor for de-energizing the whole system. The maximum load
for the Power Status output is 0.5 A and a suitable fuse should be provided.