Modbus register assignment of the ISOMETER®
55
isoEV425_D00126_09_M_XXEN/03.2019
To convert parameter data, data type descriptions are required. Text repre-
sentation is not necessary in this case.
Value Description of parameters
1023 (0x3FF) Parameter/measured value invalid.
The menu item of this parameter is not displayed.
1022 (0x3FE) No measured value/no message
1021 (0x3FD) Measured value/parameter inactive
1020 (0x3FC) Measured value/parameter only temporarily inactive (e.g.
while transmitting a new parameter). Indication in the
menu "…".
1019 (0x3FB) Parameter/measured value (value) unit not displayed
1018 (0x3FA) Parameter (code selection menu) unit not displayed
1017 (0x3F9) String max. 18 characters (e.g. device type, - variant, …)
1016 (0x3F8)
1015 (0x3F7) Time of day
1014 (0x3F6) Date: Day
1013 (0x3F5) Date: Month
1012 (0x3F4) Date: Year
1011 (0x3F3) Register address (unit not displayed)
1010 (0x3F2) Time
1009 (0x3F1) Factor multiplication [*]
1008 (0x3F0) Factor division [/]
1007 (0x3EF) Baud rate