29
TGH1266E - 05/04
Points to be Considered before Use
Kurve 2a
0
10
20
30
40
50
60
70
80
90
100
24 48 110 230
U
Nenn
(V)
C
E
(µF)
AC
3AC
DC
Curve 2a
Curve 2a: Maximum permissible system leakage capacitance in relation
to the nominal voltage, 24 ... 230 V. Up to this system leakage
capacitance, the EDS3065 has the sensitivity shown in
curve 1a.
Kurve 2b
0
0,5
1
1,5
2
2,5
3
3,5
4
4,5
5
230 400 500 690 1000
U
Nenn
(V)
C
E
(µF)
AC
3AC
DC
Curve 2b
Curve 2b: Maximum permissible system leakage capacitance in relation
to the nominal voltage 230 ... 500V. Up to this system leakage
capacitance, the EDS3065 has the sensitivity shown in
curve 1b.