22
TGH1266E - 05/04
The EDS165 in
the RCM-Mode
Operation and Settings
If the operating mode selector switch is moved to position I
∆ν
, the EDS165 operates in the RCM
mode, and can be used as a portable residual current measuring device.
The way the menus are set corresponds largely to the description already given for the EDS mode.
However, there is a difference in menu 5 (m5). In the RCM mode, the response value is set here
in mA or A respectively.
Use <ENTER> in order to start the program to
set the response value, or press <UP> to return to
the display menu.
The top line indicates the current setting of the
response value. Use the arrow keys (<UP>,
<DOWN>) to modify the response value
between 10 mA and 10 A. Up to 500 mA, the
modification is made in 10 mA steps; from 500
mA to 1 A, in steps of 50 mA; and above 50 mA, in steps of 100 mA.
Press <ENTER> to accept the set value and return to the display menu.
Note: The settings in menus m1, m2, m3 and m4 are always valid for the EDS mode and the RCM
mode.
residual current (measuring value)
response value exceeded
go on with <ENTER>
set point of response value
buzzer is activated
clamp-on probe is
connected
indication of battery
capacity
Memory= ON
RCM-mode
Y:
I∆n = 20 mA ok:
menu:
m5: set Y (I∆n)
Ι∆=
125 mA
ALARM
Y=100mA
M