SettingsSettings
EDS44x_D00201_07_M_XXDE/06.2020
39
10.3 Factory settings
Parameter Value
General information
Response value insulation fault location (I
L
) 0.5 mA (EDS441-x, EDS441-LAB)
5 mA (EDS440-x)
10 mA (EDS440-LAF)
Response value residual current measurement
(I
n
)
10 A (EDS440-x)
1 A (EDS441-x, EDS441-LAB)
Measuring current transformer type Type A: EDS440-x, EDS441-x, EDS440-LAF
Type AB: EDS441-LAB
Connection monitoring on (inactive for W…AB!)
Fault memory off
Trigger mode com
Bus type BS bus
Bus address 2
Relays
Relay K1 test on
Relay K1 operating mode N/O
Relay K1 function 1 I
L
alarm
Relay K1 function 2 off
Relay K1 function 3 off
Relay K2 test on
Relay K2 operating mode N/O
Relay K2 function 1 I
n
alarm
Relay K2 function 2 off
Relay K2 function 3 off
Channel relays 1 to 12 (optional extension with IOM441-S)
Channel relays K1...12 test on
Channel relays K1...12 operating principle N/O
Channel relays K1...12 function 1 I
L
alarm
Channel relays K1...12 function 2 I
n
alarm
Channel relays K1...12 function 3 off
Buzzer
Buzzer test on
Buzzer function 1 off
Buzzer function 1 off
Buzzer function 1 off
Digital current output (M+)
Dig. Out test off
Dig. Out function 1 off
Dig. Out function 2 off
Dig. Out function 3 off
Digital inputs
Dig. In 1 mode Active low
Dig. In 1 t(on) 100 ms
Dig. In 1 t(off) 100 ms
Dig. In 1 action Test
Dig. In 2 mode Active low
Dig. In 2 t(on) 100 ms
Dig. In 2 t(off) 100 ms
Dig. In 2 action Reset
Parameter Value