40
11. Alarm messages
Alarm message Description Measures Reference
"ALARM I
L
" LED lights
up
Channel LED lights up
The set response value of the insulation level has been
exceeded on one channel.
Determine cause of the insulation fault and eliminate it.
see "Insulation fault (ALARM
IL)" on page 27
"ALARM I
n
" LED lights
up
Channel LED lights up
The set response value of the residual current has been
exceeded on one channel.
Determine cause of the exceeded residual current and eliminate
fault.
see "Residual current
exceeded (ALARM In)" on
page 27
"SERVICE" LED lights up Internal device error
Press the TEST button
Switch the supply voltage off and on
Read out error code on the corresponding
ISOMETER®
Contact Bender service
see "Connection fault of the
current transformers" on
page 28
"SERVICE" LED lights up
Channel LED flashes
Connection fault of the current transformers
Possible causes:
Measuring current transformers defective
Power supply cable interrupted
Power supply cable short-circuited
Replace defective measuring current transformers
•Check cables
see "Connection fault of the
current transformers" on
page 28
Channel LED flashes Interferences during measurement
Possible causes:
Low-frequency residual currents
External magnetic fields
Identify interference sources and eliminate them
If several alarm messages appear at a time, the indication changes corre-
spondingly. In this case, the alarm LED and the channel LED of the faulty
channel light up together for approx. two seconds.