12.1.8 Response values EDS440-LAF for DC systems up to
a system leakage capacitance of max. 100 μF:
12.1.9 Response values EDS440-LAF for AC systems up to
a system leakage capacitance of max. 100 μF:
Nominal voltage Max. insulation fault R
F
DC 60 V
2 kOhm
DC 110 V
5 kOhm
DC 220 V
10 kOhm
DC 300 V
15 kOhm
DC 600 V
30 kOhm
DC 1000 V
50 kOhm
Nominal voltage Max. insulation fault R
F
1AC 110 V
2 kOhm
1AC 230 V
5 kOhm
1AC 400 V
10 kOhm
3AC 230 V
15 kOhm
3AC 400 V
25 kOhm
1AC 500 V
30 kOhm
1AC 690 V
40 kOhm