Technical dataTechnical data
EDS44x_D00201_07_M_XXDE/06.2020
54
Other
Operating mode........................................................................................................................................................continuous operation
Mounting............................................................................................. at an ambient temperature > 55 °C vertical mounting required
...........................................................................................................................at an ambient temperature < 55 °C mounting optional
Degree of protection internal components .........................................................................................................................................IP40
Degree of protection terminals ...........................................................................................................................................................IP20
DIN rail mounting acc. to.............................................................................................................................................................IEC 60715
Screw fixing .................................................................................................................................................... 2 x M4 with mounting clip
Enclosure material................................................................................................................................................................polycarbonate
Flammability class........................................................................................................................................................................UL 94V-0
Dimensions (W x H x D) .......................................................................................................................................................... 72 x 93 x 63
Weight...............................................................................................................................................................approx. 122 g (EDS44x-S)
...........................................................................................................................................approx. 242 g (EDS44x-L, …-LAB, …-LAF)
"W" option data deviating from the standard version
Devices with the suffix "W" feature increased shock and vibration resistance. The elec-
tronics is covered with a special varnish to provide increased protection against mechan-
ical stress and moisture.
Ambient temperatures:
Operating temperature........................................................................................................................................................-40…+70 °C
Transport..............................................................................................................................................................................-40…+85 °C
Long-term storage ..............................................................................................................................................................-25…+70 °C
Classification of climatic conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3)...............................................................................3K23 (condensation and formation of ice possible)
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3).........................................................................................................................................................3M11
1)
= At a frequency > 200 Hz, the connection of X1 and k1-12/l1-12 must be insulated.
Only permanently installed devices which at least have overvoltage category CAT2 (300 V) may be connected.
2)
= Only 50/60 Hz are permitted for UL applications.
3)
= Residual current effect of > 100mA results in a greater relative uncertainty.
13.2 Standards and certifications
Observe the applicable national and international standards. The EDS44x series meets
the device standards:
• DIN VDE 0100-410 (VDE 0100-410)
• DIN EN 61557-9 (VDE 0413-9)
• IEC 61557-9
• DIN EN 50155 (VDE 0115-200)
Subject to change! The specified standards take into account the edition valid until 11/17
unless otherwise indicated.
The operating manuals for the individual system components provide you with informa-
tion about the standards that apply to that particular device.
13.3 Ordering details
13.3.1 Insulation fault locators
* Absolute values
Type
Supply voltage U
S
*
Response value Art. No.
EDS440-S-1 DC 24 V 2…10 mA B91080201
EDS440W-S-1 DC 24 V 2…10 mA B91080201W
EDS440-L-4 AC/DC 24…240 V 2…10 mA B91080202
EDS440W-L-4 AC/DC 24…240 V 2…10 mA B91080202W
EDS441-S-1 DC 24 V 0.2…1 mA B91080204
EDS441W-S-1 DC 24 V 0.2…1 mA B91080204W
EDS441-L-4 AC/DC 24…240 V 0.2…1 mA B91080205
EDS441W-L-4 AC/DC 24…240 V 0.2…1 mA B91080205W
EDS441-LAB-4 AC/DC 24…240 V 0.2…1 mA B91080207
EDS441W-LAB-4 AC/DC 24…240 V 0.2…1 mA B91080207W
EDS440-LAF-4 AC/DC 24…240 V 10 mA B91080209