Data
42
RCM420_D00057_03_M_ XXEN/03.2021
Switching elements
Number of switching elements ............................................................................................. 2 x 1 changeover contact
Operating principle ...........................................................................N/C operation/ N/O operation (N/O operation)*
Electrical service life under rated operating conditions................................................... 10000 switching operations
Contact data acc. to IEC 60947-5-1
Utilization category AC-13 AC-14 DC-12 DC-12 DC-12
Rated operational voltage 230 V 230 V 24 V 110 V 220 V
Rated operational voltage UL 200 V 200 V 24 V 110 V 200 V
Rated operational current 5 A 3 A 1 A 0.2 A 0.1 A
Minimum contact load (relay manufacturer's reference) ......................................................................10 mA/5 V DC
Environment/EMC
EMC.............................................................................................................................................................DIN EN 62020
Operating temperature ...................................................................................................................... -25 ºC…+55 °C
Classification of climatic conditions IEC 60721 (except condensation and formation of ice)
Stationary use (IEC 60721-3-3) ................................................................................................................................ 3K5
Transportation (IEC 60721-3-2) .............................................................................................................................2K11
Storage (IEC 60721-3-1) ........................................................................................................................................1K22
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) .............................................................................................................................3M11
Transportation (IEC 60721-3-2) ..............................................................................................................................2M4
Storage (IEC 60721-3-1) .......................................................................................................................................1M12
Option "W" data different from the standard version
Classification of climatic conditions acc. to IEC 60721
Stationary use (IEC 60721-3-3) ............................................... 3K23 (condensation and formation of ice is possible)
Classification of mechanical conditions acc. to IEC 60721
Stationary use (IEC 60721-3-3) ............................................................................................................................ 3M12