Basic programs
52
VMD460-NA_D00001_05_M_XXEN/01.2020
Explanatory notes to "4105_2" settings
1)
Relay mode:
NC: The relay is energised in normal operation and deenergised in the alarm state
NO: The relay is deenergised in normal operation and energised in the alarm state
2)
Not used for VDE-AR-N 4105.2018-09
3)
Profile naming Refer to "Basic programs" on page 49.
4. df/dt Exit
1. Function off; on off off off
2. Resp. value 0.05…9.95 Hz/s 2.00 Hz/s 2.00 Hz/s 2.00 Hz/s
3. Hysteresis 1.0…50.0 % 20.0 % 20.0 % 20.0 %
4. Meas. window 50 ms…1 s 500 ms 500 ms 500 ms
5. t
(OFF)
40 ms…60 min 100 ms 100 ms 100 ms
6. t
(ON)
off 40 ms…60 min off off off
5. Vect.shift Exit
1. Function off; L1; L2; L3;single; all off off off
2. Resp. value 1.0…25.0 ° 8.0 ° 8.0 ° 8.0 °
3. t
(START-UP)
off; 40 ms…60 min 2.00 s 2.00 s 2.00 s
4. t
(ON)
off; 40 ms…60 min off off off
6. Unbalance Exit
1. Function off; on off off off
2. Resp. value 1.0…50.0 % 5.0 % 5.0 % 5.0 %
3. Hysteresis 1.0…50.0 % 20.0 % 20.0 % 20.0 %
4. t
(OFF)
40 ms…60 min 100 ms 100 ms 100 ms
7. Relays Exit
1. Relay mode
1)
NC; NO
K1: NC
K2: NC
K1: NC
K2: NC
K1: NC
K2: NC
8. Dig. input Exit
1. Mode NC; NO; off
D1: NC
D2: NC
D3: ––
2)
D4: ––
2)
D1: NC
D2: NC
D3: ––
2)
D4:––
2)
D1: NC
D2: NC
D3: ––
2)
D4: ––
2)
2. t
(START-UP)
40 ms…60 min
D1: 500 ms
D2: 500 ms
D3: ––
2)
D4: ––
2)
D1: 500 ms
D2: 500 ms
D3: ––
2)
D4: ––
2)
D1: 500 ms
D2: 500 ms
D3:––
2)
D4: ––
2)
3. Fault memory off; on
D1: on
D2: on
D1: on
D2: on
D1: on
D2: on
4105_2 Menu:
once twice
Profile 1
3)
Profile 2
3)
Profile 3
3)