Basic programs
61
VMD460-NA_D00001_05_M_XXEN/01.2020
6.6 CEI 0-21(:2012-06, :V1:2012-12, :V2:2013-12, :2014-09,
:V1:2014-12; 2016-07, V1:2017-07)
CEI 0-21 menu:
once twice
Factory
setting
Exit
1. General Exit
1. Standard 4105_2, 4105_1, 4110,
BDEW, 0126, CEI021,
C10/11, G98, G83/2, G99,
G59/2
CEI021
2. Coupling 1 AC; 3N AC; 3 AC 3N AC
3. U
(L-N)
/ U
(L-L)
50…260 V; 87…450 V U(L-N) 230 V
4. Mode
off/external
1)
/ local
2)
off
5. t
SHORT INT.
off/40 ms…60 min off
6. t
(ON) SHORT INT.
40 ms…60 min ––
7. t
(ON) NORMAL
40 ms…60 min 70 ms
8. Remote trip NC; NO; off NC
2. Voltage Exit
1. U>>
(59.S2)
off/100…150 % 115 %
2. t
(OFF) (59.S2)
40 ms…60 min 200 ms
3. U>
(59.S1)
off/100…150 % 110 %
4. t
(OFF) (59.S1)
40 ms…60 min 3.00 s
5. U
(ON) MAX
off/100…150 % off
6. U
(ON) MIN
off/1…100 % off
7. U<
(27.S1)
off/1…100 % 85 %
8. t
(OFF) (27.S1)
40 ms…60 min 400 ms
9. U<<
(27.S2)
off/1…100 % 40 %
10. t
(OFF) (27.S2)
40 ms…60 min 200 ms