Basic programs
62
VMD460-NA_D00001_05_M_XXEN/01.2020
3. Frequency Exit
1. f>> off/50.00…65.00 Hz off
2. t
(OFF)
40 ms…60 min ––
3. f>
(81>.S1)
off/50.00…65.00 Hz 50.50 Hz
4. t
(OFF) (81>.S1)
40 ms…60 min 100 ms
5. f
(ON) MAX
off/50.00…65.00 Hz off
6. f
(ON) MIN
off/45.00…60.00 Hz off
7. f<
(81<.S1)
off/45.00…60.00 Hz 49.50 Hz
8. t
(OFF) (81<.S1)
40 ms…60 min 100 ms
9. f>
(81>.S2)
off/50.00…65.00 Hz 51.50 Hz
10. f<
(81<.S2)
off/50.00…65.00 Hz 47.50 Hz
11. Tlc
(off) (81>.S2)
40 ms…60 min 100 ms
12. Tlc
(off) (81>.S2)
40 ms…60 min 100 ms
13. Tex
(off) (81>.S2)
40 ms…60 min 1.00 s
3. Frequency 14. Tex
(off) (81<.S2)
40 ms…60 min 4.00 s
15. f<< off; 45.00…60.00 Hz off
16. t
(OFF)
40 ms…60 min ––
4. df/dt Exit
1. Function off/on off
2. Resp. value 0.05…9.95 Hz/s 1.00 Hz/s
3. Hysteresis 1.0…50.0 % 20.0 %
4. Meas. window 50 ms…1 s 200 ms
5. t
(OFF)
40 ms…60 min 100 ms
6. t
(ON)
off; 40 ms…60 min 30 s
5. Vect.shift Exit
1. Function off; L1; L2; L3; single; all off
2. Resp. value 1.0…25.0 ° 8.0 °
3. t
(START-UP)
off/40 ms…60 min 2.00 s
4. t
(ON)
off/40 ms…60 min 30 s
6. Unbalance Exit
1. Function off/on off
2. Resp. value 1.0…50.0 % 5.0 %
3. Hysteresis 1.0…50.0 % 20.0 %
4. t
(OFF)
40 ms…60 min 100 ms
7. Relays Exit
1. Relay mode
1)
NC; NO K1: NC
K2: NO
CEI 0-21 menu:
once twice
Factory
setting