Loading...
Basic programs
72
VMD460-NA_D00001_05_M_XXEN/01.2020
6.11 G59/2:2010, -1/2011
G59/2 menu:
once twice
Factory
setting
Exit
1. General Exit
1. Standard 4105_2; 4105_1; 4110;
BDEW; 0126; CEI021;
C10/11; G98; G83/2;
G99; G59/2
G59/2
2. Coupling 1 AC; 3N AC; 3 AC 3N AC
3. U
(L-N)
/ U
(L-L)
50…260 V; 87…450 V U(L-N) 230 V
4. t
SHORT INT.
off; 40 ms…60 min off
5. t
(ON) SHORT INT.
40 ms…60 min ––
6. t
(ON) NORMAL
40 ms…60 min 180 s
7. Remote trip NC; NO; off off
2. Voltage Exit
1. U>> off; 100…150 % 115 %
2. t
(OFF)
40 ms…60 min 500 ms
3. U > off; 100…150 % 110 %
4. t
(OFF)
40 ms…60 min 1.00 s
5. U
(ON) MAX
off; 100…150 % off
6. U
(ON) MIN
off; 1…100 % off
7. U < off; 1…100 % 87 %
8. t
(OFF)
40 ms…60 min 2.50 s
9. U<< off; 1…100 % 80 %
10. t
(OFF)
40 ms…60 min 500 ms
3. Frequency Exit
1. f>> off; 50.00…65.00 Hz 52.00 Hz
2. t
(OFF)
40 ms…60 min 500 ms
3. f> off; 50.00…65.00 Hz 51.50 Hz
4. t
(OFF)
40 ms…60 min 90 s
5. f
(ON) MAX
off; 50.00…65.00 Hz off
6. f
(ON) MIN
off; 45.00…60.00 Hz off
7. f< off; 45.00…60.00 Hz 47.50 Hz
8. t
(OFF)
40 ms…60 min 20 s
9. f<< off; 45.00…60.00 Hz 47.00 Hz
10. t
(OFF)
40 ms…60 min 500 ms