Basic programs
56
VMD460-NA_D00001_05_M_XXEN/01.2020
Explanatory notes to "4110" settings
1)
Relay mode:
NC: The relay is energised in normal operation and deenergised in the alarm state
NO: The relay is deenergised in normal operation and energised in the alarm state
2)
Not used for VDE-AR-N 4110:2018-11
3)
Profile naming Refer to "Basic programs" on page 49.
4. df/dt
Exit
1. Function off; on off off off off
2. Resp. value 0.05…9.95 Hz/s 1.00 Hz/s 1.00 Hz/s 1.00 Hz/s 1.00 Hz/s
3. Hysteresis 1.0…50.0 % 20.0 % 20.0 % 20.0 % 20.0 %
4. Meas. window 50 ms…1 s 200 ms 200 ms 200 ms 200 ms
5. t
(OFF)
40 ms…60 min 100 ms 100 ms 100 ms 100 ms
6. t
(ON)
off 40 ms…60 min off off off off
5. Vect.shift
Exit
1. Function off; L1; L2; L3; single; all off off off off
2. Resp. value 1.0…25.0 ° 8.0 ° 8.0 ° 8.0 ° 8.0 °
3. t
(START-UP)
off; 40 ms…60 min 2.00 s 2.00 s 2.00 s 2.00 s
4. t
(ON)
off; 40 ms…60 min off off off off
6. Unbalance
Exit
1. Function off; on off off off off
2. Resp. value 1.0…50.0 % 5.0 % 5.0 % 5.0 % 5.0 %
3. Hysteresis 1.0…50.0 % 20.0 % 20.0 % 20.0 % 20.0 %
4. t
(OFF)
40 ms…60 min 100 ms 100 ms 100 ms 100 ms
7. Relays
Exit
1. Relay mode
1)
NC; NO K1: NC
K2: NC
K1: NC
K2: NC
K1: NC
K2: NC
K1: NC
K2: NC
8. Dig. input
Exit
1. Mode NC; NO; off D1: off
D2: off
D3; D4: ––
2)
D1: off
D2: off
D3; D4: ––
2)
D1: off
D2: off
D3; D4: ––
2)
D1: off
D2: off
D3; D4: ––
2)
2. t
(START-UP)
40 ms…60 min D1: ––
D2: ––
D3; D4: ––
2)
D1: ––
D2: ––
D3; D4: ––
2)
D1: ––
D2: ––
D3; D4: ––
2)
D1: ––
D2: ––
D3; D4: ––
2)
3. Fault memory off; on D1: off
D2: off
D3; D4: ––
2)
D1: off
D2: off
D3; D4: ––
2)
D1: off
D2: off
D3; D4: ––
2)
D1: off
D2: off
D3; D4: ––
2)
4110 Menu :
once twice
Profile 1
3)
Profile 2
3)
Profile 3
3)
Profile 4
3)