5.2 Setting values for nozzle assembly B 30
5.3 Setting values for air damper B 30
Grade of Oil Excess air flue gases Max. % CO
2
% O
2
% CO
2
Lambda 1.2
Light oil, B10 heating oil/
biofuel blend (as defined in
DIN V51603-6)
3–5 ≈12,5 15,4
Prior to commissioning, the basic settings of the burner can be set
in accordance with the diagram. See under Basic settings Note that
it is simply a matter of a basic setting that should be adjusted
retrospectively once the burner has started. A flue gas analysis and
soot quantity measurement must be carried out when fine-tuning the burner.
Recomended exsess air