As close
as possible
Pipe
Diameter
"D"
Rigid Wall Flexible
Suction Hose with
quick connect shown.
Eccentric Reducer
flat side up.
Short length of
straight pipe.
(2 times pipe diameter)
Connection for remote hand primer
or for manual priming.
4 x "D"
minimum
1 x "D" minimum
from bottom
Strainer / Foot Valve
To keep debris from entering
pump suction and to maintain
pump prime after shut-off.
Connection for optional Engine Exhaust
Primer. Locate at least one (1) pipe
diameter from pump case.
Portable Installation is most
common with this style pump.
Typical of permanant
installation using standard
pipe and fittings.
Suction
Gauge
Eccentric Reducer
flat side up.
Support pipe
as required
Standard or long
radius elbow.
Slope upward
to pump.
Straight run, short as possible but
at least 6 times pipe diameter ("D")
after elbow to stabilize flow.
All connections must
be
air tight.
NOTICE:
Companion
Flange Kit
Companion
Flange Kit
Companion
Flange Kits
• Recommendations called out in field of drawing apply to
both suction connections shown.
• Use pipe, tubing or reinforced hose to make suction con-
nection. Hose must have sufficient strength to resist col-
lapse under pressure differential that occurs while pump is
running.
• Suction pipe size should be at least one commercial pipe
size larger that opening in pump inlet. Flow velocity should
not exceed 8 ft./sec.
• Suction screen area must be at least four times suction pipe
area.
• Net Positive Suction Head Available (NPSHA) must exceed
Net Positive Suction Head Required (NPSHR) by the pump
or reduced performance and severe pump damage may
result.
• All suction piping must have a continuous rise to the pump
suction inlet. For rigid pipe or tubing, a 1/4 inch per foot
minimum slope is recommended.