EasyManua.ls Logo

Biddle Comfort Circle Series - Page 26

Default Icon
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INSTALLATION COMFORT CIRCLE
26
2.15.2 Input in controller
The controller has one input signal interface, to which a timer
is usually connected.
The signal switches the unit on or off. Depending on the set-
ting 1 in the timer menu, the unit either can or cannot be
switched on or off using the
=-key (see section 5).
The operation is global – the signal affects all units connected
to the controller.
Caution:
c The input is designed for controls with potential-free con-
tacts, and is not to be loaded.
2.15.3 Input in unit
The unit has one input signal interface 1, to which a timer, a
low-limit or room thermostat or a BMS signal may be con
-
nected.
The effect of the input signal depends on the controller set-
tings. (see section 4.2.3). A signal to one unit will have the
same effect on all units linked with that unit.
Caution:
c The input is designed for controls with potential-free con-
tacts, and is not to be loaded.
2.15.4 Outputs in unit
The unit has interfaces 2 for three output signals: these can
be used for, for instance, controlling the central-heating or
cooling system, or for transmitting status reports to a BMS.
Caution:
c The outputs are potential-free contacts (relays). Their
maximum load is 24V and 1A.
Danger:
d Connect SELV circuits only – Safety Extra Low
Voltage circuits.
The function of the outputs depends on the controller setting
(see section
4.3.3).
1
1
2

Table of Contents

Related product manuals