KB-206-1 11
6.3 Pipelines
The pipelines must be as short as possible in order to
minimise pressure drops and to keep the refrigerant
quantity available in the pipeline system as low as pos-
sible.
!
!
NOTICE
During soldering work on the suction gas line,
protect the low pressure transmitter against ex-
cess heat (max. 120°C)!
6.4 Incorporation of the condensing unit into the
refrigeration system
If the ECOLITE condensing unit is positioned above the
evaporator, the suction gas line must be executed ac-
cordingly. In case of a long suction gas line or several
evaporators, the use of the optionally available oil sep-
arator and OLC is recommended.
When using an LHL5E with only one capacity-con-
trolled cylinder bank, the suction gas line must be ex-
ecuted such that the oil return is guaranteed even at a
minimum capacity of 50%.
If the ECOLITE condensing unit is positioned below the
evaporator, an additional subcooler should be provided
(example see figure 9, page 11).
6
7
7
2
4
5
1
Fig.8: Mounting of the ECOLITE above the evaporator
6
4
1
2
5
3
Fig.9: Mounting of the ECOLITE below the evaporator
Connection positions
1 ECOLITE condensing unit
2 Evaporator
3 Additional subcooler
4 Expansion valve
5 Liquid line
6 Suction gas line
7 Oil syphon
Tab.3: Connection positions

Table of Contents

Other manuals for Bitzer ECOLITE LHL3E/2CES-3Y

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bitzer ECOLITE LHL3E/2CES-3Y and is the answer not in the manual?

Bitzer ECOLITE LHL3E/2CES-3Y Specifications

General IconGeneral
BrandBitzer
ModelECOLITE LHL3E/2CES-3Y
CategoryHeat Pump
LanguageEnglish

Related product manuals