44
Configuration and adjustment variables
(1)Note:The speed is limited by parameter HSP (page 27).
Modbus
address
CANopen
address
Code
Read/
Write
Name/Description/Possible values
11410 2054 / B SP2 R/W 2
nd
preset speed
Unit: 0.1 Hz
Factory setting: 100
Adjustment range: 0 to 5000 (1)
11411 2054 / C SP3 R/W 3
rd
preset speed
Unit: 0.1 Hz
Factory setting: 150
Adjustment range: 0 to 5000 (1)
11412 2054 / D SP4 R/W 4
th
preset speed
Unit: 0.1 Hz
Factory setting: 200
Adjustment range: 0 to 5000 (1)
11413 2054 / E SP5 R/W 5
th
preset speed
Unit: 0.1 Hz
Factory setting: 250
Adjustment range: 0 to 5000 (1)
11414 2054 / F SP6 R/W 6
th
preset speed
Unit: 0.1 Hz
Factory setting: 300
Adjustment range: 0 to 5000 (1)
11415 2054 / 10 SP7 R/W 7
th
preset speed
Unit: 0.1 Hz
Factory setting: 350
Adjustment range: 0 to 5000 (1)
11416 2054 / 11 SP8 R/W 8
th
preset speed
Unit: 0.1 Hz
Factory setting: 400
Adjustment range: 0 to 5000 (1)
11417 2054 / 12 SP9 R/W 9
th
preset speed
Unit: 0.1 Hz
Factory setting: 450
Adjustment range: 0 to 5000 (1)
11418 2054 / 13 SP10 R/W 10
th
preset speed
Unit: 0.1 Hz
Factory setting: 500
Adjustment range: 0 to 5000 (1)
11419 2054 / 14 SP11 R/W 11
th
preset speed
Unit: 0.1 Hz
Factory setting: 550
Adjustment range: 0 to 5000 (1)
11420 2054 / 15 SP12 R/W 12
th
preset speed
Unit: 0.1 Hz
Factory setting: 600
Adjustment range: 0 to 5000 (1)
11421 2054 / 16 SP13 R/W 13
th
preset speed
Unit: 0.1 Hz
Factory setting: 700
Adjustment range: 0 to 5000 (1)
11422 2054 / 17 SP14 R/W 14
th
preset speed
Unit: 0.1 Hz
Factory setting: 800
Adjustment range: 0 to 5000 (1)
11423 2054 / 18 SP15 R/W 15
th
preset speed
Unit: 0.1 Hz
Factory setting: 900
Adjustment range: 0 to 5000 (1)
11424 2054 / 19 SP16 R/W 16
th
preset speed
Unit: 0.1 Hz
Factory setting: 1000
Adjustment range: 0 to 5000 (1)