45
Configuration and adjustment variables
(1) Note: The "+/- speed" function is incompatible with several functions (see page 14). Before configuring it, these functions must be
unassigned, especially the summing inputs (set SA2 to nO page
42) and the preset speeds (set PS2 and PS4 to nO page 42) which are
assigned in the factory settings.
Modbus
address
CANopen
address
Code
Read/
Write
Name/Description/Possible values
11110 2051 / B JOG R/WS Jog operation
Factory setting: if tCC = 0 or 2: 0 if tCC = 1: 132
Selecting the assigned logic input activates the function.
0 = "nO": Not assigned
129 = "LI1": Logic input LI1
130 = "LI2": Logic input LI2
131 = "LI3": Logic input LI3
132 = "LI4": Logic input LI4
133 = "LI5": Logic input LI5
134 = "LI6": Logic input LI6
Note, the "JOG operation" function may be incompatible with other (see page
14).
11111 2051 / C JGF R/W Jog operation reference
Unit: 0.1 Hz
Factory setting: 100
Adjustment range: 0 to 100
11501 2055 / 2 USP R/WS + speed (motorized potentiometer)
Factory setting: 0
Function active only if LAC = L2 or L3 and UPdt has been selected (see page 35).
Selecting the assigned logic input activates the function (1).
0 = "nO": Not assigned
129 = "LI1": Logic input LI1
130 = "LI2": Logic input LI2
131 = "LI3": Logic input LI3
132 = "LI4": Logic input LI4
133 = "LI5": Logic input LI5
134 = "LI6": Logic input LI6
11502 2055 / 3 dSP R/WS -speed (motorized potentiometer)
Factory setting: 0
Function active only if LAC = L2 or L3 and UPdt has been selected (see page 35).
Selecting the assigned logic input activates the function (1).
0 = "nO": Not assigned
129 = "LI1": Logic input LI1
130 = "LI2": Logic input LI2
131 = "LI3": Logic input LI3
132 = "LI4": Logic input LI4
133 = "LI5": Logic input LI5
134 = "LI6": Logic input LI6
11503 2055 / 4 Str R/WS Save reference
Factory setting: 0
Associated with the "+/- speed" function, this parameter can be used to save the reference:
- When the run commands disappear (saved to RAM)
- When the line supply or the run commands disappear (saved to EEPROM)
On the next start-up, the speed reference is the last reference saved.
0 = "nO": No save
1 = "rAM": Save to RAM
2 = "EEP": Save to EEPROM
11901 2059 / 2 PIF R/WS PI regulator feedback
Factory setting: 0
0 = "nO": Not assigned
1 = "AI1": Analog input AI1
2 = "AI2": Analog input AI2
3 = "AI3": Analog input AI3
Note The "PI Regulator" function is incompatible with several functions (see page 14). Before
configuring it, these functions must be unassigned, especially the summing inputs (set SA2 to
nO page 42) and the preset speeds (set PS2 and PS4 to nO page 42) which are assigned in
the factory settings.
11941 2059 / 2A rPG R/W PI regulator proportional gain
Unit: 0.01
Factory setting: 100
Adjustment range: 1 to 10000
Contributes to dynamic performance during rapid changes in the PI feedback.