Models 3.2 - 13.2, controller µchiller
Blue Box - Page 65
SYMPTOM
OPERATION
PROBABLE CAUSE
POSSIBLE CORRECTIVE ACTION
COOLING
HEATING
C)
No compressor
running.
No water flow at
evaporator
Check hydraulic system
(display On with alarm
"FL")
Faulty flow switch Check contact of flow switch
and replace if necessary
D)
No compressor
running. Fans stopped
(display On with alarm
“F1” or “F2”)
(only version LC and
LC/HP)
Fan thermal protection
intervention
Check insulation between
windings and between windings
and earth; replace fan if
necessary.
E)
No compressor
running. (display On
with alarm "A1")
No consent of defrost
thermostat due to
insufficient water flow rate
Check hydraulic circuit and wait
until the water temperature
exceeds the value necessary for
the unit to restart
No consent of defrost
thermostat due to
insufficient glycol
concentration
The programmed set-point is too
low for the percentage of glycol
in the circuit. Increase the glycol
percentage and reduce the
defrost set-point.
F)
No compressor
running. (display On,
with alarm "E1")
Connections to evaporator
inlet temperature sensor
interrupted
Restore correct connection of
temperature sensor
Evaporator inlet
temperature sensor faulty
Replace temperature sensor