Models 3.2 - 13.2, controller µchiller
Blue Box - Page 66
SYMPTOM
OPERATION
PROBABLE CAUSE
POSSIBLE CORRECTIVE ACTION
COOLING
HEATING
G)
No compressor
running. (display On,
with alarm "E3" or
Resistance RK3 or RK4
faulty or disconnected (only
version LC and LC/HP)
Check resistance and replace if
necessary
"E5")
Connections to pressure
sensor interrupted (HP
version only or if
condensation pressure
control with fan speed
regulator is fitted with
version LC and LC/HP)
Restore correct connections to
pressure sensor ("E3" refers to
compressor 1, "E5" refers to
compressor 2)
Faulty pressure sensor (only
on HP version or if
condensation pressure
control with fan speed
regulator is fitted with
version LC and LC/HP)
Replace pressure sensor ("E3"
refers to compressor 1, "E5"
refers to compressor 2)
H)
Unit runs with
insufficient capacity
(Display On without
Insufficient refrigerant
charge
Check refrigerant circuits with
leak detector, repair leak and
recharge circuit
alarms)
Presence of moisture in
refrigerant circuit
Replace refrigerant filter and, if
necessary, dehydrate and
recharge circuit
One compressor fails to
start, power circuit open
and compressor contactor
energised
Find and eliminate the cause of
the protection intervention;
change the fuses.
If the fuses blow immediately,
replace the compressor.
A compressor fails to start,
fuses are OK and
compressor contactor is de-
energised
Check voltage across compressor
contactor coil and continuity of
coil; if necessary, replace coil
4-way reversing valve
locked or coil faulty
Check power supply and coils of
valves and replace valves if
necessary