EasyManua.ls Logo

Blue Box SIGMA 2002 - Page 73

Blue Box SIGMA 2002
124 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Models 3.2 - 13.2, controller µchiller
Blue Box - Page 67
SYMPTOM
OPERATION
PROBABLE CAUSE
POSSIBLE CORRECTIVE ACTION
COOLING
HEATING
I)
Compressor 1 and/or 2
not working (display
Circuit overcharged (only
version LC and LC/HP)
Check refrigerant charge and
remove if necessary;
On with alarm
“H1” and/or “H2”)
High pressure switch faulty Check and replace if necessary
Coil filters clogged; air flow
too low (version LC and
LC/HP)
Clean filters with compressed air
Presence of incondensable
gas in the refrigerant circuit
Empty circuit, apply vacuum, and
recharge
Fans faulty (version LC and
LC/HP)
Check and replace fans
Faulty circulating pump Check and replace
Defrost-end pressure switch
not working (only version
LC/HP)
Check and replace
Metallic filter of condenser
clogged
Clean filter
Insufficient condenser
water flow
Check hydraulic circuit and
condenser water flow
Condenser entering water
temperature too high
Check condenser hydraulic circuit

Table of Contents

Related product manuals