Models 3.2 - 13.2, controller µchiller
Blue Box - Page 68
SYMPTOM
OPERATION
PROBABLE CAUSE
POSSIBLE CORRECTIVE ACTION
COOLING
HEATING
L)
Compressor 1 and/or 2
not working (display
On with alarm “L1”
and/or “L2”)
Refrigerant circuit
completely empty
Check refrigerant circuit with
leak detector after pressurising to
approximately 4 bar. Repair leak,
apply vacuum, charge circuit.
Low pressure switch faulty Check and replace if necessary
Metallic coil filter clogged;
air flow too low (only
LC/HP)
Clean filter with compressed air
Refrigerant filter clogged Check and replace if necessary
Faulty water circulator
pump
Check and replace if necessary
Defrost pressure switch
with incorrect setting (only
version LC/HP)
Check and correct setting
Liquid refrigerant valve not
completely open (if present)
Check and open fully
Thermostatic expansion
valve not operating
correctly
Check, clean, or replace if
necessary
Evaporator metallic filter
clogged
Clean the filter
Evaporator circulating
pump faulty
Check, and replace if necessary