EasyManua.ls Logo

Blue Box SIGMA 2002 - Page 75

Blue Box SIGMA 2002
124 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Models 3.2 - 13.2, controller µchiller
Blue Box - Page 69
SYMPTOM
OPERATION
PROBABLE CAUSE
POSSIBLE CORRECTIVE ACTION
COOLING
HEATING
M)
Compressor 1 and/or 2
not working (display
On with alarm
Insufficient refrigerant
charge
Find leak with leak detector,
repair, and recharge circuit
“C1” and/or “C2”)
4-way valve locked Replace valve
Lack of oil Check quantity of oil in circuit
and replenish as necessary.
Check that the circuit has all the
necessary measures to ensure oil
return to the compressor
Condenser entering water
temperature too high
Check temperature and flow of
condenser entering water
N)
Ice on liquid refrigerant
pipe
Liquid refrigerant filter
clogged
Replace filter
Valve on liquid refrigerant
line (if present) not
completely open
Open valve fully
O)
Compressors run
constantly
Operating thermostat
incorrectly set or faulty
Check setting; replace
thermostat if necessary
Lack of refrigerant gas
charge
Check and recharge if necessary
Excess thermal load Reduce thermal load

Table of Contents

Related product manuals