Models 14.4 - 26.4, controller pCO
2
Blue Box - Page 80
SYMPTOM
OPERATION
PROBABLE CAUSE
POSSIBLE CORRECTIVE ACTION
COOLING
HEATING
A)
No compressor running
(display Off)
No mains power Check presence of mains power
Main power switch Off
(position "O")
Turn main power selector to
position "I"
Transformer fuses and/or
fuses 24 V burnt-out
Check fuses and if necessary
replace burned out fuses (FU50
and FU51). If fuses burn-out
again call for assistance
Electronic control card
faulty
Call assistance
B)
No compressor
running. Display On:
”OFF from external
consent”
No external consent Check presence of external
consent; if not present, bridge
terminals 1 and 2
C)
No compressor
running. Display On:
”OFF from supervision
system”
No consent from
supervision system
Activate operation from
supervision system
D)
No compressor
running. Display On:
”OFF”
No consent from “on/off”
key of user interface
Press “on/off” key