Models 14.4 - 26.4, controller pCO
2
Blue Box - Page 81
SYMPTOM
OPERATION
PROBABLE CAUSE
POSSIBLE CORRECTIVE ACTION
COOLING
HEATING
E1)
No compressor
running. Display On:
unit ON with alarm
High Pressure
Compressor 1, 2, 3, 4”
220V fuses burnt-out
(FU51) (in version LC and
LC/HP also the alarm “Fans
protection” will be
displayed)
Change fuses. If fuses burn-out
again contact assistance
Insufficient condenser
water flow
Check hydraulic circuit and
condenser water flow
Entering condenser water
temperature too high
Check hydraulic circuit of
condenser
The unit has an excessive
refrigerant charge (only
version LC and LC/HP)
Call assistance
Remote condenser faulty
(only LC version LC and
LC/HP)
E2)
No compressor
running. Display On:
Entering condenser water
temperature too high
Check flow and temperature of
condenser entering water
unit ON with alarm
“Thermal protections
Compressor 1, 2, 3, 4”
Drop in power feeding
voltage
Check voltage stability and fit
appropriate protection if
necessary
Setting of thermal
protections
Contact assistance
Circuits partially discharged Call service to replenish charge