Models 14.4 - 26.4, controller pCO
2
Blue Box - Page 82
SYMPTOM
OPERATION
PROBABLE CAUSE
POSSIBLE CORRECTIVE ACTION
COOLING
HEATING
E3)
No compressor
running. Display On:
Insufficient percentage of
glycol in hydraulic circuit
Restore correct glycol percentage
unit ON with alarm
“Low Pressure
Compressor 1, 2, 3, 4”
Both circuits have
insufficient refrigerant
charge
Find possible leaks in circuit,
repair, and recharge
Incorrect setting of defrost
set-point (only version
LC/HP)
Check and correct setting if
necessary
E4)
No compressor
running. Display On:
unit ON with alarm
Insufficient water flow to
evaporator
Increase water flow to
evaporator and check
temperature rise
“Exceeded Threshold
Low Temperature of
leaving User Water”.
Faulty controller Contact service organisation
E5)
No compressor
running. Display On:
unit ON with alarm
“Exceeded Threshold
High Temperature of
Excessive thermal load Wait until entering water
temperature is below the alarm
set point. Start hydraulic circuit
of evaporator and unit. If not
sufficient contact assistance.
entering User Water
Refrigerant circuits partially
discharged
Call assistance
E6)
(Only version LC)
No compressor
running. Display On:
unit ON with alarm
“Fans protection
Depending upon the fan
type installed
Check thermal consent of fans