Models 14.4 - 26.4, controller pCO
2
Blue Box - Page 83
SYMPTOM
OPERATION
PROBABLE CAUSE
POSSIBLE CORRECTIVE ACTION
COOLING
HEATING
E7)
No compressor
running. Display On:
unit ON with alarm
“No power to Control
circuits”
Power supply voltage not
stable
Check power supply voltage; if
not correct contact the electricity
company
F1)
No compressor
running.
No water flow to
evaporator
Check hydraulic circuit
Display On: unit
OFF with alarm
“Flow Switch Alarm”
Flow switch faulty Check flow switch contact and
replace if necessary
F2)
No compressor
running. Display On:
unit OFF with alarm
Incorrect Phase
Sequence” and phase
sequence relay with
green LED On and
orange LED Off
Incorrect phase sequence Invert two of the phase wires of
the power supply line
F3)
No compressor
running. Display On:
unit OFF with alarm
Incorrect Phase
Sequence” and phase
sequence relay with
green and orange LEDs
On
Faulty relay Check to ensure that relay closes
contact
F4)
No compressor
running. Display On:
unit OFF with alarm
Fuses FU56 burnt-out Check fuse FU56 and replace if
necessary
”Incorrect Phase
Sequence”
and phase sequence
relay with green and
orange LEDs Off
One of the three phases is
not present
Check connection of each phase