Models 14.4 - 26.4, controller pCO
2
Blue Box - Page 84
SYMPTOM
OPERATION
PROBABLE CAUSE
POSSIBLE CORRECTIVE ACTION
COOLING
HEATING
G)
No compressor
running. Display On:
No consent from digital
input to compressors
Check consent to compressors
and close relative contacts
unit ON without alarm
Unit at temperature Normal operation
Compressor fuses burnt-
out
Check continuity of fuses; if
burnt-out call service
Controller faulty Call service
H1)
Only 1 compressor
running. Display On
Excess refrigerant charge Check refrigerant charge and call
service organisation
with alarm
“High Pressure
Compressor 1 and 2 or
3 and 4”
Problems at the condenser
hydraulic circuit
Check flow and temperature of
condenser entering water
High pressure switch
incorrectly calibrated or
faulty
Check pressure switch setting
Pressostatic valve
incorrectly set
Check setting of pressostatic
valve and call assistance
H2)
Only 1 compressor
running. Display On
with alarm
Insufficient refrigerant
charge due to a leak in the
circuit
Call service
“Low Pressure
Compressor 1 and 2 or
3 and 4”
Thermostatic valve faulty Call service
Solenoid valve of liquid
refrigerant line faulty (if
present)
Call service
Dehydrating filter clogged Call service