Models 14.4 - 26.4, controller pCO
2
Blue Box - Page 85
SYMPTOM
OPERATION
PROBABLE CAUSE
POSSIBLE CORRECTIVE ACTION
COOLING
HEATING
H3)
One, two or three
compressors running.
Display On with alarm
“Compressor Thermal
Protections”
Problems at the compressor
Call service
I)
Only one compressor
Unit capacity step active Normal operation
Running.
Display On
without alarms
Fuses burnt-out Call service
Controller faulty Call service
No external consent to the
compressor
Check external consent of
compressor
L1)
All compressors
running. Display On
with alarm
“Compressor
Maintenance”
Compressors specified by
alarm require maintenance
Call service for scheduled
maintenance
L2)
All compressors
running. Display On
with alarm “Unit
Maintenance”
Unit maintenance required Call service for scheduled
maintenance
M)
All compressors
Excess thermal load Call service
running without
stopping. Display
On without alarm
Refrigerant circuits partially
discharged
Call service
Controller not working Call service