-1-
1. Safety and EMC Instructions
Please carefully read the following user manual and
safety instructions before installing and using the UPS!
1.1 Installation
Check installation instructions before connecting to UPS to the
supply.
Condensation may occur if the UPS is transported directly from a
cold to a warm environment. Please allow an acclimatization time
of at least two hours before switching the UPS.
Do not install the UPS near a water source or in a damp
environment.
Do not install the UPS where it would be exposed to direct
sunlight or near a heat source.
Do not connect items of equipment which would overload the
UPS (e.g. laser printers) to the UPS output.
Always place cables in such a way so that they are not a trip
hazard.
Always make sure the installation is connected to a reliable earth
source.
Any additional battery cabinets must be connected to a reliable
earth source.
Check after installation, the total earth leakage current including
the UPS and the connected load does not exceed 3.5mA.
Do not obstruct the ventilation and air flow of the UPS housing.
Ensure the air vents on the front, side and rear of the UPS are not
blocked. Allow at least 25cm of space on each side.