ACS 553, ACS 563 Service Manual
1 689 975 295 2021-04-13Robert Bosch GmbH
33
Diagnostics and Testing
4. When the test is complete, select
icon to return to the Service Menu.
The input test displays the current state of
the measurable parts of the unit such as the
amount of refrigerant, temperatures, and the
various pressures present within the unit.
The values shown are absolute and indicate
what is happening within the unit at any given
moment during operation. The values are
observable only and cannot be changed or
deleted. They can indicate whether a sensor
or device is operating within the required limits
for proper unit operation.
1. From the Service Menu, scroll to .
2. Select icon. The following displays:
Placeholders X and Y represent numbers
displayed during this test. A list of the sensors and
devices and what the values represent follows:
ISV Weight X.XXXYY ISV Weight
LS Press X.XYYY Low-Side Pressure
AC Press X.XYYY Accumulator
Pressure
ISV Temp X.X
0
Y ISV Temperature
HP Sw X High-Pressure Switch
Air Flow XXXXrpm Fan Air Flow
(for R1234yf only)
3. Scroll through the sensors or devices to
icon to return to the Service Menu.
the correct volume to make sure enough air is
present to prevent the buildup of refrigerant and
to keep the compressor temperature below its
upper limit.
1. From the Service Menu, scroll to
.
2. Select icon. The following displays:
3. Check :
• All body panels are installed.
• Fan is clean and running.
4. Select icon, and wait unit is performing
calibration automatically.
5. If calibration succeeds, unit will return to
service menu.
6. If calibration fails, unit will prompt user to
retry.
Displays internal storage vessel (ISV) pressure
and temperature.
1. From the Service Menu, scroll to
.
2. Select icon. The following displays:
3. Scroll to the and
keep
incondensable gas from tank.