test emits a brief tone, and for 60 seconds the display indicates
that the point was tested. The tone and display verify that each
detection device is working properly. Keypads within the area’s
scope from which you did not initiate the walk test show Walk
test in progress during the testing.
Notice!
Fire walk test includes gas
When you perform a Fire walk test, the security system
tests any 24-hour points that are not invisible, including
gas points.
Performing a walk test:
1. Open the Main menu.
2. Press [Actions] to open the menu.
3. Press [Test] to open the menu.
4. Press [Walk Test] to open the menu.
5. Press [Fire], [Intrusion], [Service], or [Invisible] based upon
the type of walk test you wish to perform.
6. The keypad shows the number of points remaining to test.
Press [View Untested Points].
7. Use
/[NEXT] to go through your desired point and view the
status of that point.
8. Escape from the menu.
Control Panels B94x/B93x Actions menu | en 75
Bosch Security Systems, Inc. 2015.01 | 02 | F.01U.307.371