Technical information
33
Compress 3000 AWES – 6720892204 (2020/06)
CAUTION:
Physical injury or material damage due to incorrect temperature
If sensors with incorrect characteristics are used, the temperatures may
be too high or too low.
▶ Make sure that the temperature sensors used comply with the
specified values (see tables below).
Table 13 Sensor T0, TC0, TC1
Table 14 Sensor TW1
Table 15 Sensor T1
°C °C °C °C
20 12488 40 5331 60 2490 80 1256
25 10001 45 4327 65 2084 85 1070
30 8060 50 3605 70 1753 90 915
35 6536 55 2989 75 1480 - -
°C °C °C °C
20 14772 40 6653 60 3243 80 1704
25 11981 45 5523 65 2744 85 1464
30 9786 50 4608 70 2332 90 1262
35 8047 55 3856 75 1990 - -
°C °C °C
– 40 154300 5 11900 50 1696
– 35 111700 10 9330 55 1405
– 30 81700 15 7370 60 1170
– 25 60400 20 5870 65 980
– 20 45100 25 4700 70 824
– 15 33950 30 3790 75 696
– 10 25800 35 3070 80 590
– 5 19770 40 2510 85 503
0 15280 45 2055 90 430