Installation
Bosch Condens 5000W – 6 720 646 195 (2018/10)
26
Reducing the telescopic flue length
Correct orientation of flue terminal
▶ Ensure that the “top” label is facing up before securing the flue
section to the turret.
The flue terminal must be fitted with the 'top' label uppermost to allow
the correct fit and use of the plume management system.
▶ Remove securing screws [3] to detach the terminal assembly from
the turret.
▶ Slide terminal section [2] from the terminal assembly [1] and
discard the terminal section [2].
Fig. 35 Reducing the standard terminal
▶ To use terminal assembly [1] without cutting remove the location lug
[4] on the inner flue tube [5]and remove any burrs.
Further flue length reduction of the terminal assembly:
▶ Mark the length required for the terminal as shown (min. 130mm)
and cut square, taking care not to damage the tubes.
▶ Remove any burrs and chamfer the outer edge of the tubes to assist
ease of connection and prevent seal damage.
Fig. 36 Further terminal assembly reduction
The aluminium tape is not required when reducing the terminal.
Installing the telescopic flue
Refer to figure 37.
1. Set the flue length to the distance required, secure with screws
provided.
2. Seal the joint with the aluminium tape provided.
3. Slide the inner wall seal onto the terminal.
4. If fitting from inside the building; slide the outer wall seal onto the
terminal.
Fig. 37 Telescopic flue preparation
The turret securing screws are from the boiler and are not in flue kit.
Refer to figures 38 & 39.
1. Remove the three inner flue tube retaining screws [2]. The inner tube
will be held in place in the boiler.
2. Check the boiler flue seal is correctly seated and apply silicone
grease.
3. Position terminal through the flue opening in the wall to the outside of
the building by the distance shown.
4. Align the flue turret to the boiler flue outlet with flat facing [1] to the
rear of the boiler.
The flue turret should be pushed straight down, on to the boiler.
Fig. 38 Aligning the flue turret
▶ Fit the screws removed in step 1 to secure flue turret.
6720643895-31.1Wo
2
3
1
4
5
6
1
130 mm
265 mm
MIN
6720643895-32.2Wo
3.
4.
1.
1.
2.
TOP
6720644842-08.1Wo
1
2
6720643895-35.2Wo