Inspection and maintenance
43
Condens 7000 FP – 6721846699 (2022/12)
Fig. 56 Undo the connecting cable and nuts on the ignition transformer
[1] Ignition cable
[2] Ignition cable
[3] Monitor lead
[4] Fixing nuts (4x)
[5] Ignition transformer connecting cable
Fig. 57 Pull the burner back
[1] Mixture manifold
11.8 Cleaning the burner and heat exchanger
11.8.1 Clean the burner
With intensive contamination, the burner rod may be separated from the
mixture manifold and blown-out using a blower gun (max. 3 bar).
Blow out the burner rod from the outside to the inside and vacuum
clean inside.
Mount the burner rod with new gasket again.
11.8.2 Clean the heat exchanger
DANGER
Danger to life through escaping flue gas!
During installation, look out for faulty gaskets and ensure they are
seated correctly. Replace faulty gaskets.
Replace the gaskets as described ( Chapter 11.11.4, page 48).
Dry and/or wet clean the heat exchanger.
Shut down the heating system ( Chapter 9, page 33).
Close the gas main shutoff valve or gas isolator.
Allow floor standing boiler to cool down.
Remove the front panels and corresponding side panels.
Place the tundish that collects dirt and condensate residues under
the condensation catch pan.
Pull the siphon [1] off the drainage connection of the condensation
catch pan [2] and out of the drain pipe. Turn slightly sideways in
doing so.
Fig. 58 Removing the siphon
[1] Siphon
[2] Condensation catch pan outlet
Remove the screws from the cover of the condensation catch pan.