6 720 820 872 (2016/12)CR 400 | CW 400 | CW 800
Commissioning | 21
Menu item Question Answer / setting
Start configuration wizard Check before starting the configuration wizard:
Module installed and address set?
Remote control installed and set?
Temperature sensor installed?
Start the configuration wizard? Yes | No
System data Low loss hdr.
sensr. instll.
Is a low loss header installed? If yes, is a temperature
sensor installed? If yes, where is it electrically
connected?
No low-loss header | At the
boiler | At the module | Header w/
o sensor
Config. DHW at
boiler
How is DHW connected to the heat source (boiler)? No DHW | 3-way valve | Primary
pump
Config. of HC1 at
boiler
Is heating circuit 1 connected to the heat source
(boiler)? If yes, does it have a separate heating circuit
pump?
No heating circuit | No own
heating circuit pump | Own pump
Min. outdoor
temperature
With weather-compensated control: what is the
minimum outside temperature at the location on
average over the last few years?
– 35 ... 10 °C
Type of building To what type of building is the heated building? Light | Medium | Heavy
Boiler data Pump type Is the pump operated depending on the burner output
or the differential pressure?
Output-compensated | Delta P-
compensated 1...4
Pump run-on
time
How long must the pump run on after the shutdown of
the burner to discharge the heat from the heat source?
24h | 1 ... 60 min
Heating circuit
1
Heating circuit
installed
Is heating circuit 1 installed? If yes, where is heating
circuit 1 electrically connected?
No | At the boiler | At the module
Ctrl type h. circ.
1
How should the temperature influenced by heating
circuit 1 be controlled?
Outdoor-temp.-compensated |
Outside temp. with low end |
Room-temp.-compensated |
Room temperature output |
Constant
User interface What user interface is installed? CR400 | CW400 | CW800 |
CR100 | CR10
Heating system
heat circ. 1
What type of heating does heating circuit 1 operate? Radiator | Convector heater |
Underfloor
Set point
constant
If heating circuit 1 is configured as constant heating
circuit: To which temperature should the heating be
controlled?
30 ... 85 °C
Max. flow
temperature
What is the maximum flow temperature that should be
set?
E.g. 30 ... 85 °C
Set heating
curve
Should the heating curve for heating circuit 1 be set?
(For further sub-settings Æ Chapter 7.1.3, from
page 32)
Æ page 35, Tab. 16
Setback type Which setback type should be used? Reduced mode | Outside
temperature threshold | Room
temperature threshold
Table 9 Commissioning with the configuration wizard