D6412/D4412 Operation and Installation Guide
Page 20 © 2003 Bosch Security Systems45349E
D6412/D4412
Power Supply
CAUTION
Investigate low battery reports immediately: If primary (AC) power is off and the discharge continues, the panel
becomes inoperative when the battery voltage drops below 10.2 VDC.
4.2.5 Battery Charging Circuit - Float Charge
The float voltage for the battery charging circuit is 13.5 VDC to 13.9 VDC at a maximum current of 1.4 A.
4.2.6 Battery Discharge/Recharge Schedule
Discharge Cycle
AC Off: Command centers indicate trouble. AC Fail Report sent as programmed.
13.8 VDC: Charging float level
12.1 VDC: Low battery trouble at command centers. Low Battery Report as programmed.
10.2 VDC: Panel shuts down as voltage falls below 10.2 VDC
Recharge Cycle
AC On: Panel restarts, battery charging begins, AC Restoral Report sent as programmed, AC trouble clears from
command centers.
13.0 VDC: Battery restoral reports sent, battery trouble clears from command centers
13.8 VDC: Battery float charged.
4.2.7 System Status LED
The System Status LED shows system status, including power supply status as described in Table 4. See Figure 4 for the
location of the LED on the panel.
System Status LED Display
System Normal
On for 50 ms; Off for 1 sec.
Battery Missing
Off for 200 ms; On for 1 sec.
AC Missing
Off for 200 ms; On for 200 ms
Off for 200 ms; On for 1 sec.
Phone Ringing
Flickers for 1 sec. as each ring is detected.
Phone Line Seized (panel using phone line)
On solid.
Shut Down (system voltage below 10.2 VDC)
Off for 200 ms; On for 200 ms
Off for 200 ms; On for 200 ms
Off for 200 ms; On for 1 sec.
Table 4: System Status LED Description
4.3 External Power Supply
The external power supply (not supplied) is not intended to provide power to
indicating devices for burglary and fire applications.
Burglary Applications use a UL603 Listed burglar alarm power supply
with an operating voltage range of
11.8 VDC to 12.4 VDC for Bank Safe/Vault applications (72 hrs. of
standby battery required).
Fire Applications use a UL1481 Listed power supply operating voltage
range of 11.8 VDC to 12.4 VDC for fire applications.