D6412/D4412 Operation and Installation Guide
Page 64 © 2003 Bosch Security Systems45349E
D6412/D4412
Troubleshooting
16.1.3 Command Center Issues
Problem Cause Solution
Entered Cmd 50 at my
Command Center but it does
not let me move to specific
areas.
Cmd 50 (Move to Area) is
disabled if there are no points
assigned to a particular area.
Program at least one point and assign it to the
particular area. Cmd 50 should work as defined.
16.1.4 Programming Issues
Problem Cause Solution
Cannot enter into
Programmer’s Mode.
One or more areas are armed;
keypad programming may be
disabled; Installer’s Switch may
be open.
If one or more areas are armed, disarm all
armed areas. Programmer’s Mode cannot be
entered while one or more areas are armed.
However, an Installer’s Keypad can access the
Programming Mode regardless of the panel’s
arming state.
Programming may be disabled. See
Programming Options, Installer Switch, and
Daylight Savings Time Options (Nibble 0257) in
the D6412/D4412 Program Entry Guide (P/N:
45351.) Make sure the following options are
enabled: Installer Switch, Keypad
Programming, and PK32 (Programming Key).
To enter Programmer’s Mode, the Installer
Switch must be closed. See the following
sections in this installation guide for details:
3.4.2 Closing the Installer Switch and 13.2
Entering the Installer Mode.
Enabled Open/Close Reports,
but when in the Panel Part On
Mode, these reports are still
not sent.
Open/Close Reports for Part On
Mode is not programmed
correctly.
In Areas of the D6412/D4412 Program Entry Guide
(P/N: 45351), see the Area # Opening/Closing
Reporting Options parameter. Enable
“Opening/Closing Reports for Part On Modes” for
Nibbles 0296, 0318, 0340, and 0362.
PK32 does not work (upload,
download, erase, etc.)
PK32 has not been enabled in the
panel firmware.
In Nibble 0257, enable PK32. See Section 2.5
Programming Options in the D6412/D4412 Program
Entry Guide (P/N: 45351).
The off-board points added to
the system display as missing.
Device Location parameter is not
programmed correctly.
See Locations in the D6412/D4412 Program Entry
Guide (P/N: 45351). Verify which device type was
added (e.g., RF point, off-board point, etc.). In the
Device Location parameter, enter the correct value
based on the Device Parameter Selections
(1 = on-board; 2 = DX2010; 3 = DX2010, Doubled;
4 = RF Receiver 1: 5 = RF Receiver 2). Point
configuration is locked into only those configuration
types in the Device Parameter Selections.
Panel is not following report
routing as programmed.
Lock Area Reporting parameter is
enabled.
Set the Lock Area Reporting parameter to 0
(disabled). See the D6412/D4412 Program Entry
Guide (P/N: 45351) for more information.
16.1.5 Miscellaneous Issues
Problem Cause Solution
Entered Cmd 50 at my
Command Center but it won’t
let me move to specific areas.
Cmd 50 (Move to Area) is
disabled if there are no points
assigned to a particular area.
Program at least one point and assign it to the
particular area. Cmd 50 should work as defined.