D6412/D4412 Operation and Installation Guide
Page 40 © 2003 Bosch Security Systems45349E
D6412/D4412
On-Board Outputs
Unexpected Output at PO1 to PO4: If these outputs do not provide the alarm output you expect:
Check the programming for Programmable Outputs in the Outputs section of the D6412/D4412 Program Entry
Guide (P/N: 45351).
Check the Point Index Configuration section of the D6412/D4412 Program Entry Guide to verify the points you
are activating are programmed for alarm output.
I
MPORTAN
T
If Programmable Output 2 is configured as a supervised siren driver (in combination with the Alrm + terminal),
you must connect a 4
or
8 Ω 8 Ω
8 Ω 8 Ω
8 Ω
siren/speaker to PO 2 to clear the siren/speaker supervision trouble.