D8125 Operation and Installation Guide
D8125
Page 20 © 2004 Bosch Security Systems, Inc.74-04247-000-N
Installation
Default values are shown in ( ) and in
bold
D9412/D911
RADXPNTS Handle
Point Assignments (001 through 045)
POPIT Switch
Setting
Tr an s
*
Point
#
Point
Index
Area
Assign
Debounce
(1-15)
BFSK/
Relay Point Text
Note: D9412 uses points from 001 - 127, 129 - 247
[ 001 __ _3
1 _____ 2 _____ 1 _____
P1 FIRE
200 002 __ _1
1
_____
2
_____
2
_____
P2 PANIC
300 003 _ 2 _5
1
_____
2
_____
3
_____
P3 DELAY
400 004 _ 1 _3
1
_____
2
_____
4
_____
P4 FOLLOW
500 005 __ _7
1
_____
2
_____
5
_____
P5 INSTANT
600 006 __ _7
1
_____
2
_____
6
_____
P6 INSTANT
700 007 __ _7
1
_____
2
_____
7
_____
P7 INSTANT
800 008 __ _7
1 _____ 2 _____ 8 _____
P8 INSTANT
0 1 2 3 4 5 6
101 009 __ __
1 _____ 2 _____ 1 _____
P9
0 1 2 3 4 5 -
102 010 __ __
1 _____ 2 _____ 1 _____
P10
0 1 2 3 4 - 6
103 011 __ __
1
_____
2
_____
1
_____
P11
0 1 2 3 4 - -
104 012 __ __
1
_____
2
_____
1
_____
P12
0 1 2 3 - 5 6
105 013 __ __
1 _____ 2 _____ 1 _____
P13
0 1 2 3 - 5 -
106 014 __ __
1
_____
2
_____
1
_____
P14
0 1 2 3 - - 6
107 015 __ __
1
_____
2
_____
1
_____
P15
3.1.6 POPIT Module Point Assignments
Six switches on each D8127 POPIT assign the module to a point number. D9127 ASIC POPITs have seven switches (0-6) that
assign the module to a point number. POPIT switch settings are found in the Point Assignment section of the D9412G/
D7412G Program Record Sheet (P/N: 47488). See Figure 6 .
For the D9412/D9112, point numbers 73 to 127 and 193 to 247 must use D9127 POPITs. Points 9 to 72 and 129 to
192 may use either D8127 or D9127 POPITs. For the D7412/D7212, Points 9 to 72 may use either D8127 or D9127
POPITs; however, D9127 POPITs must be used for
Points 73-75.
3.1.6.1 Program Record Sheet
The first column on the program record sheet contains the switch
settings for the POPITs. Switches are numbered 1 to 6, left to right
on the D8127 POPIT. Switches are numbered 0 to 6, left to right on
the D9127 POPIT. Set switches whose number appears in the
setting to the ON position. Set switches with a dash (-) in the
switch position to the OFF position (see Figure 4).
The second column contains the translation of the point number
into the ZONEX format. See Point User Flag in the Panel Wide
Parameters module of the D9412G/D7412G Program Entry Guide
(P/N: 47775) for an explanation of this feature.
The third column contains the point number as it is displayed at command centers.
The fourth column contains the point index. See the Point Index Parameters module in the D9412G/D7412G Program Entry
Guide (P/N: 47775) for an explanation of the point index.
The fifth column of the Program Record Sheet shows the area the point is assigned to. The sixth column shows the Debounce
Count for the point. See Debounce Count in the Point Assignments module in the D9412G/D7412G Program Entry Guide (P/
N: 47775).
The seventh column shows the BFSK report code. It is the point number reported for this point when the panel is using the
BFSK format. The eighth column contains the text displayed at command centers for the point. The text is transmitted to the
receiver when the panel is using the Modem IIIa
2
format.
3.1.6.2 POPIT Labels
Off-board points for the D9412 and D9112 are numbered 9 to 127 and 129 to 247 (D7412 and D7212 use Points 9 through 75
only). The D9412/D9112 reserves Points 128 and 248 for internal use. You must connect POPITs for Points 129 through 247
to expansion loops connected to POPEX #2.
Two sheets of peel-off POPIT labels are supplied with the D8125 POPEX module. Use the sheet marked Bank1 for Points 9 to
127. Use the sheet marked Bank2 for Points 129 to 247.
Each label has two parts. Place the smaller part, with just the point number on it, on the chip. Place the larger part with the
switch settings on the base of the POPIT. Set the switches and cover the POPIT.
Do not program two POPITs for the same point number. After you program all the points, perform a service walk test. The
Troubleshooting section of this document contains instructions for performing a service walk test. If a point does not test,
check the programming for a duplicate address switch settings.
3.2 D9112B1/D7212B1
Save the POPIT Label Sheets: The D8125 is packaged with two sets of POPIT label sheets. One is marked for use
with the D9112B1. Save this set. You will use it later to label the POPITs.
Figure 4: Program Record Sheet